Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
14A883 Power ups.Counted power ups
15A885 DC charge.Counted DC charges
0 / real32Displays the actual present value of value counter 1.
The value of the source selected by parameter 33.53
Value counter 1 source is read at one-second intervals
and added to the counter. A divisor can be applied to
the count (see 33.54 Value counter 1 divider).
When the counter exceeds the limit set by 33.51 Value
counter 1 warn limit, bit 4 of 33.1 Counter status is set
to 1.
The warning specified by 33.55 Value counter 1 warn
message is also given if enabled by 33.52 Value counter
1 function.
The counter can be reset from the Drive Composer PC
tool, or from the control panel by keeping Reset
depressed for over 3 seconds.
Value counter 1
actual
33.50
- / -Actual present value of value counter 1.-2147483000...2147483000
- / real32Sets the limit for value counter 1.
With a positive limit, bit 4 of 33.1 Counter status is set
to 1 (and a warning optionally generated) when the
counter is equal or greater than the limit.
With a negative limit, bit 4 of 33.1 Counter status is set
to 1 (and a warning optionally generated) when the
counter is equal or smaller than the limit.
0 = Counter disabled.
Value counter 1 warn
limit
33.51
- / -Limit for value counter 1.-2147483000...2147483000
- / uint16Configures value counter 1.Value counter 1
function
33.52
0 = Loop: When the limit is reached, the counter is reset.
The counter status (bit 4 of 33.1) switches to 1 for one
second. The warning (if enabled) stays active for at
least 10 seconds.
1 = Saturate: When the limit is reached, the counter
status (bit 4 of 33.1) switches to 1, and remains so until
33.50 is reset. The warning (if enabled) also stays active
until 33.50 is reset.
Counter modeb0
0 = Disable: No warning is given when the limit is
reached
1 = Enable: A warning (see 33.55) is given when the limit
is reached
Warning enableb1
Reservedb2…15
1 = 10000h…FFFFh
Not selected / uint32Selects the signal to be monitored by value counter 1.Value counter 1
source
33.53
0None (counter disabled).Not selected
11.1 Motor speed used.Motor speed
See Terms and abbreviations (page 169).Other [bit]
394 Parameters