Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / uint16Status of the motor fan control logic.
Bit 1 is the control output for the fan, to be selected as
the source of, for example, a digital or relay output.
The other bits indicate the statuses of the selected
control and feedback sources, and the fault status.
This parameter is read-only.
DOL starter status
word
35.105
Status of fan control source selected by 35.100.
0 = Stop requested
1 = Start requested
Start command:b0
Fan control bit (delays observed). Select this bit as the
source of the output controlling the fan.
0 = Stopped
1 = Started
Delayed start
command:
b1
Status of fan feedback (source selected by 35.103).
0 = Stopped
1 = Running
DOL feedback:b2
Fault status.
0 = Fault (fan feedback missing). The action taken is
selected by 35.106.
1 = No fault
DOL fault (-1):b3
Reservedb4…15
1 = 10000h…FFFFh
Fault / uint16Selects the action taken when missing fan feedback is
detected by the motor fan control logic.
DOL starter event
type
35.106
0No action taken.No action
1The drive generates a warning (A781 Motor fan).Warning
2Drive trips on 71B1 Motor fan.Fault