Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Not selected / uint32Selects, together with 40.20 Set 1 internal setpoint sel2,
the internal setpoint out of the presets defined by
parameters 40.2140.24.
Setpoint
preset active
Source defined by
par. 40.20
Source defined by
par. 40.19
1 (par. 40.21)00
2 (par. 40.22)01
3 (par. 40.23)10
4 (par. 40.24)11
Set 1 internal
setpoint sel1
40.19
00Not selected
11Selected
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
See Terms and abbreviations (page 169).Other [bit]
Not selected / uint32Selects, together with 40.19 Set 1 internal setpoint sel1,
the internal setpoint out of the presets defined by
parameters 40.2140.24. See table at 40.19 Set 1
internal setpoint sel1.
Set 1 internal
setpoint sel2
40.20
00Not selected
11Selected
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
See Terms and abbreviations (page 169).Other [bit]
424 Parameters