ABB ACS880 - Page 425

ABB ACS880
764 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / real32Defines process setpoint preset 1. See parameter 40.19
Set 1 internal setpoint sel1.
The unit is selected by parameter 40.12 Set 1 unit
selection.
Set 1 internal
setpoint 1
40.21
1 = 1 / 100 = 1Process setpoint preset 1.-32768.00 ...
32767.00
- / real32Defines process setpoint preset 2. See parameter 40.19
Set 1 internal setpoint sel1.
The unit is selected by parameter 40.12 Set 1 unit
selection.
Set 1 internal
setpoint 2
40.22
1 = 1 / 100 = 1Process setpoint preset 2.-32768.00 ...
32767.00
- / real32Defines process setpoint preset 3. See parameter 40.19
Set 1 internal setpoint sel1.
The unit is selected by parameter 40.12 Set 1 unit
selection.
Set 1 internal
setpoint 3
40.23
1 = 1 / 100 = 1Process setpoint preset 3.-32768.00 ...
32767.00
- / real32Defines process setpoint preset 4. See parameter 40.19
Set 1 internal setpoint sel1.
The unit is selected by parameter 40.12 Set 1 unit
selection.
Set 1 internal
setpoint 4
40.24
1 = 1 / 100 = 1Process setpoint preset 4.-32768.00 ...
32767.00
Setpoint source 1 /
uint32
Configures the selection between setpoint sources 1
(40.16) and 2 (40.17).
This parameter is only effective when parameter 40.18
Set 1 setpoint function is set to In1 or In2.
0 = Setpoint source 1
1 = Setpoint source 2
Set 1 setpoint
selection
40.25
00.Setpoint source 1
11.Setpoint source 2
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
See Terms and abbreviations (page 169).Other [bit]
0.00 / real32Defines a minimum limit for the process PID controller
setpoint.
Set 1 setpoint min40.26
Parameters 425