Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
See Terms and abbreviations (page 169).Other [bit]
On / uint32Selects a source that enables/disables process PID
control.
See also parameter 40.7 Set 1 PID operation mode.
0 = Process PID control disabled.
1 = Process PID control enabled.
Set 1 PID activation
source
40.60
00.Off
11.On
2Process PID control is disabled when external control
location
EXT1 is active, and enabled when external control
location
EXT2 is active.
See also parameter 19.11 Ext1/Ext2 selection.
Follow Ext1/Ext2
selection
3Digital input DI1 (10.2 DI delayed status, bit 0).DI1
4Digital input DI2 (10.2 DI delayed status, bit 1).DI2
5Digital input DI3 (10.2 DI delayed status, bit 2).DI3
6Digital input DI4 (10.2 DI delayed status, bit 3).DI4
7Digital input DI5 (10.2 DI delayed status, bit 4).DI5
8Digital input DI6 (10.2 DI delayed status, bit 5).DI6
11Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
12Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
See Terms and abbreviations (page 169).Other [bit]
0.00 / real32Storage parameter for receiving a process feedback
value eg. through the embedded fieldbus interface.
The value can be sent to the drive as Modbus I/O data.
Set the target selection parameter of that particular
data (58.10158.124) to Feedback data storage. In 40.8
Set 1 feedback 1 source (or 40.9 Set 1 feedback 2
source), select Feedback data storage.
Feedback data
storage
40.91
100 = 1 / 100 = 1Storage parameter for process feedback.-327.68 ... 327.67