Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / -“Above limit” indication trigger level for speed control.
For scaling, see parameter 46.1.
0.00 ... 30000.00
rpm
50.00 Hz / real32Defines the trigger level for “above limit” indication in
frequency control. When actual frequency exceeds the
limit, bit 10 of 6.17 Drive status word 2 is set.
Above frequency
limit
46.32
- / -“Above limit” indication trigger level for frequency
control. For scaling, see parameter 46.2.
0.00 ... 1000.00 Hz
300.0 % / real32Defines the trigger level for “above limit” indication in
torque control. When actual torque exceeds the limit,
bit 10 of 6.17 Drive status word 2 is set.
Above torque limit46.33
- / -“Above limit” indication trigger level for torque control.
For scaling, see parameter 46.3.
0.0 ... 1600.0 %
1 / uint16Defines the number of decimal places of torque-related
parameters.
Torque decimals46.42
1 = 1 / 1 = 1Number of decimal places of torque parameters.0...2
0 / real32Defines the custom scaling value for fieldbus reference.
When this value is
• set to 0, the used reference = FB ref * 75.19 /
20000
• not set to 0, the used reference = FB ref /46.200
FB reference scaler46.200
1 = 1 / 1 = 1Fieldbus reference scaling value.0...30000
Parameters 455