Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
3The scaling is defined by parameter 46.3 Torque scaling.Torque
4The scaling is defined by parameter 46.1 Speed scaling.Speed
5The scaling is defined by parameter 46.2 Frequency
scaling.
Frequency
Auto / uint16Selects the type and scaling of reference 2 received
from fieldbus adapter A.
See parameter 50.4 FBA A ref1 type.
FBA A ref2 type50.5
Auto / uint16Selects the type/source and scaling of actual value 1
transmitted to the fieldbus network through fieldbus
adapter A.
Note: Fieldbus-specific communication profiles may
use different scalings. For more information, see the
manual of the fieldbus adapter.
FBA A actual 1 type50.7
0Type/source and scaling follow the type of reference
1 selected by parameter 50.4 FBA A ref1 type. See the
individual settings below for the sources and scalings.
Auto
1The value selected by parameter 50.10 FBA A act1
transparent source is sent as actual value 1. No scaling
is applied (the 16-bit scaling is 1 = 1 unit).
Transparent
2The value selected by parameter 50.10 FBA A act1
transparent source is sent as actual value 1 with a 16-bit
scaling of 100 = 1 unit (ie. integer and two decimals).
General
31.10 Motor torque is sent as actual value 1. The scaling
is defined by parameter 46.3 Torque scaling.
Torque
41.1 Motor speed used is sent as actual value 1. The
scaling is defined by parameter 46.1 Speed scaling.
Speed
51.6 Output frequency is sent as actual value 1. The
scaling is defined by parameter 46.2 Frequency scaling.
Frequency
6Motor position is sent as actual value 1. See parameter
90.6 Motor position scaled.
Position
Auto / uint16Selects the type/source and scaling of actual value 2
transmitted to the fieldbus network through fieldbus
adapter A.
See parameter 50.7 FBA A actual 1 type.
FBA A actual 2 type50.8
Not selected / uint32Selects the source of the fieldbus status word when
the fieldbus adapter is set to a transparent
communication profile eg. by its configuration
parameters (group 51 FBA A settings).
FBA A SW
transparent source
50.9
0No source selected.Not selected
See Terms and abbreviations (page 169).Other [value]
Not selected / uint32When parameter 50.7 FBA A actual 1 type is set to
Transparent or General, this parameter selects the
source of actual value 1 transmitted to the fieldbus
network through fieldbus adapter A.
FBA A act1
transparent source
50.10
0No source selected.Not selected
See Terms and abbreviations (page 169).Other [value]
Parameters 465