Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Configuration of the embedded fieldbus (EFB)
interface.
Embedded fieldbus58
See also chapter Fieldbus control through the
embedded fieldbus interface (EFB) (page 705).
None / uint16Enables/disables the embedded fieldbus interface and
selects the protocol to use.
Protocol enable58.1
Note:
• When the embedded fieldbus interface is enabled,
the drive-to-drive link functionality is automatically
disabled.
• This parameter cannot be changed while the drive
is running.
0None (communication disabled).None
1Embedded fieldbus interface is enabled and uses the
Modbus RTU protocol.
Modbus RTU
0 / uint16Displays the protocol ID and revision.
This parameter is read-only.
Protocol ID58.2
1 = 1Protocol ID and revision.0000…FFFFh
1 / uint16Defines the node address of the drive on the fieldbus
link. Values 1…247 are allowable. Two devices with the
same address are not allowed on-line.
Node address58.3
Changes to this parameter take effect after the control
unit is rebooted or the new settings validated by
parameter 58.6 Communication control.
1 = 1 / 1 = 1Node address (values 1…247 are allowable).0...255
19.2 kbps / uint16Selects the transfer rate of the fieldbus link.
Changes to this parameter take effect after the control
unit is rebooted or the new settings validated by
parameter 58.6 Communication control.
Baud rate58.4
14.8 kbit/s.4.8 kbps
29.6 kbit/s.9.6 kbps
319.2 kbit/s.19.2 kbps
438.4 kbit/s.38.4 kbps
557.6 kbit/s.57.6 kbps
676.8 kbit/s.76.8 kbps
7115.2 kbit/s.115.2 kbps
8 EVEN 1 / uint16Selects the type of parity bit and the number of stop
bits.
Parity58.5
Changes to this parameter take effect after the control
unit is rebooted or the new settings validated by
parameter 58.6 Communication control.
0Eight data bits, no parity bit, one stop bit.8 NONE 1
1Eight data bits, no parity bit, two stop bits.8 NONE 2
480 Parameters