Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0Type/source and scaling follow the type of reference
1 selected by parameter 58.26 EFB ref1 type. See the
individual settings below for the sources and scalings.
Auto
1The value selected by parameter 58.31 EFB act1
transparent source is sent as actual value 1. No scaling
is applied (the 16- bit scaling is 1 = 1 unit).
Transparent
2The value selected by parameter 58.31 EFB act1
transparent source is sent as actual value 1 with a 16-bit
scaling of 100 = 1 unit (ie. integer and two decimals).
General
31.10 Motor torque is sent as actual value 1. The scaling
is defined by parameter 46.3 Torque scaling.
Torque
41.1 Motor speed used is sent as actual value 1. The
scaling is defined by parameter 46.1 Speed scaling.
Speed
51.6 Output frequency is sent as actual value 1. The
scaling is defined by parameter 46.2 Frequency scaling.
Frequency
6Motor position is sent as actual value 1. See parameter
90.6 Motor position scaled.
Position
Torque / uint16Selects the type/source and scaling of actual value 2
transmitted to the fieldbus network through the
embedded fieldbus interface.
EFB act2 type58.29
0Type/source and scaling follow the type of reference
2 selected by parameter 58.27 EFB ref2 type. See the
individual settings below for the sources and scalings.
Auto
1The value selected by parameter 58.32 EFB act2
transparent source is sent as actual value 2. No scaling
is applied (the 16- bit scaling is 1 = 1 unit).
Transparent
2The value selected by parameter 58.32 EFB act2
transparent source is sent as actual value 2 with a 16-bit
scaling of 100 = 1 unit (ie. integer and two decimals).
General
31.10 Motor torque is sent as actual value 2. The scaling
is defined by parameter 46.3 Torque scaling.
Torque
41.1 Motor speed used is sent as actual value 2. The
scaling is defined by parameter 46.1 Speed scaling.
Speed
51.6 Output frequency is sent as actual value 2. The
scaling is defined by parameter 46.2 Frequency scaling.
Frequency
6Motor position is sent as actual value 1. See parameter
90.6 Motor position scaled.
Position
Not selected / uint32Selects the source of the status word when 58.25
Control profile is set to Transparent.
EFB status word
transparent source
58.30
0None.Not selected
See Terms and abbreviations (page 169).Other [value]
Not selected / uint32Selects the source of actual value 1 when 58.28 EFB act1
type is set to Transparent or General.
EFB act1 transparent
source
58.31
0None.Not selected
See Terms and abbreviations (page 169).Other [value]
Parameters 485