Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
4The scaling is defined by parameter 46.1 Speed scaling.Speed
5The scaling is defined by parameter 46.2 Frequency
scaling.
Frequency
Torque / uint16Selects the type and scaling of reference 2 received
from the master/follower link. The resulting value is
shown by 3.14 M/F or D2D ref2.
For the selections, see parameter 60.10 M/F ref1 type.
M/F ref2 type60.11
Auto / uint16Selects the type/source and scaling of actual value
ACT1 transmitted to the master/follower link.
M/F act1 type60.12
0Type/source and scaling follow the type of reference
1 selected by parameter 60.10 M/F ref1 type. See the
individual settings below for the sources and scalings.
Auto
1Reserved
2Reserved
31.10 Motor torque is sent as actual value 1. The scaling
is defined by parameter 46.3 Torque scaling.
Torque
41.1 Motor speed used is sent as actual value 1. The
scaling is defined by parameter 46.1 Speed scaling.
Speed
51.6 Output frequency is sent as actual value 1. The
scaling is defined by parameter 46.2 Frequency scaling.
Frequency
Auto / uint16Selects the type/source and scaling of actual value
ACT2 transmitted to the master/follower link.
M/F act2 type60.13
0Type/source and scaling follow the type of reference
2 selected by parameter 60.11 M/F ref2 type. See the
individual settings below for the sources and scalings.
Auto
1Reserved
2Reserved
31.10 Motor torque is sent as actual value 2. The scaling
is defined by parameter 46.3 Torque scaling.
Torque
41.1 Motor speed used is sent as actual value 2. The
scaling is defined by parameter 46.1 Speed scaling.
Speed
51.6 Output frequency is sent as actual value 2. The
scaling is defined by parameter 46.2 Frequency scaling.
Frequency
None / uint32(Effective in the master only.) Defines the followers
from which data is read. See also parameters
62.2862.33.
M/F follower
selection
60.14
2Data is read from the follower with node address 2.Follower node 2
4Data is read from the follower with node address 3.Follower node 3
8Data is read from the follower with node address 4.Follower node 4
6Data is read from the followers with node addresses 2
and 3.
Follower nodes 2+3
10Data is read from the followers with node addresses 2
and 4.
Follower nodes 2+4