Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
12Data is read from the followers with node addresses 3
and 4.
Follower nodes 3+4
14Data is read from the followers with node addresses
2, 3 and 4.
Follower nodes
2+3+4
0None.None
FALSE / uint32When parameter 60.3 M/F mode is set to DDCS forcing
or D2D forcing, this parameter selects a source that
forces the drive to be the master on the
master/follower link.
1 = Drive is master on the master/follower link
Force master60.15
00.FALSE
11.TRUE
See Terms and abbreviations (page 169).Other [bit]
FALSE / uint32When parameter 60.3 M/F mode is set to DDCS forcing
or D2D forcing, this parameter selects a source that
forces the drive to be a follower on the master/follower
link.
1 = Drive is follower on the master/follower link
Force follower60.16
00.FALSE
11.TRUE
See Terms and abbreviations (page 169).Other [bit]
Fault / uint16(Effective in the master only.) Selects how the drive
reacts to a fault in a follower.
See also parameter 60.23 M/F status supervision sel 1.
Note: Each follower must be configured to transmit its
status word as one of the three data words in
parameters 60.160.3. In the master, the
corresponding target parameter (62.462.12) must be
set to Follower SW.
Follower fault action60.17
0No action taken. Unaffected drives on the
master/follower link will continue running.
No action
1The drive generates a warning (AFE7 Follower).Warning
2Drive trips on FF7E Follower. All followers will be
stopped.
Fault
Always / uint16Interlocks the starting of the master to the status of
the followers.
See also parameter 60.23 M/F status supervision sel 1.
Note: Each follower must be configured to transmit its
status word as one of the three data words in
parameters 60.160.3. In the master, the
corresponding target parameter (62.462.12) must be
set to Follower SW.
Follower enable60.18
0The master can only be started if all followers are ready
to switch on (bit 0 of 6.11 Main status word in each
follower is on).
MSW bit 0
Parameters 493