Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0 = Status of follower 20 is monitored continuously.
1 = Status of follower 20 is monitored only when it is
in stopped state.
Follower 20b3
0 = Status of follower 21 is monitored continuously.
1 = Status of follower 21 is monitored only when it is in
stopped state.
Follower 21b4
0 = Status of follower 22 is monitored continuously.
1 = Status of follower 22 is monitored only when it is in
stopped state.
Follower 22b5
0 = Status of follower 23 is monitored continuously.
1 = Status of follower 23 is monitored only when it is in
stopped state.
Follower 23b6
0 = Status of follower 24 is monitored continuously.
1 = Status of follower 24 is monitored only when it is in
stopped state.
Follower 24b7
0 = Status of follower 25 is monitored continuously.
1 = Status of follower 25 is monitored only when it is in
stopped state.
Follower 25b8
0 = Status of follower 26 is monitored continuously.
1 = Status of follower 26 is monitored only when it is in
stopped state.
Follower 26b9
0 = Status of follower 27 is monitored continuously.
1 = Status of follower 27 is monitored only when it is in
stopped state.
Follower 27b10
0 = Status of follower 28 is monitored continuously.
1 = Status of follower 28 is monitored only when it is in
stopped state.
Follower 28b11
0 = Status of follower 29 is monitored continuously.
1 = Status of follower 29 is monitored only when it is in
stopped state.
Follower 29b12
0 = Status of follower 30 is monitored continuously.
1 = Status of follower 30 is monitored only when it is
in stopped state.
Follower 30b13
0 = Status of follower 31 is monitored continuously.
1 = Status of follower 31 is monitored only when it is in
stopped state.
Follower 31b14
0 = Status of follower 32 is monitored continuously.
1 = Status of follower 32 is monitored only when it is in
stopped state.
Follower 32b15
1 = 10000h…FFFFh
60.0 s / uint16Defines a wake-up delay during which no
master/follower communication faults or warnings are
generated. This is to allow all drives on the
master/follower link to power up.
The master cannot be started until the delay elapses
or all monitored followers are found to be ready.
M/F wake up delay60.31
10 = 1 s / 10 = 1 sMaster/follower wake-up delay.0.0 ... 180.0 s
Parameters 499