Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
3Drive generates an A7CA DDCS controller comm loss
warning and sets the speed to the speed defined by
parameter 22.41 Speed ref safe (or 28.41 Frequency ref
safe when frequency reference is being used). This only
occurs if control is expected from the external
controller, or if supervision is forced using parameter
60.65 DDCS controller comm supervision force.
WARNING!
Make sure that it is safe to continue operation
in case of a communication break.
Speed ref safe
4Drive trips on 7581 DDCS controller comm loss. This
occurs even though no control is expected from the
external controller.
Fault always
5Drive generates an A7CA DDCS controller comm loss
warning. This only occurs if control is expected from
the external controller, or if supervision is forced using
parameter 60.65 DDCS controller comm supervision
force.
WARNING!
Make sure that it is safe to continue operation
in case of a communication break.
Warning
Auto / uint16Selects the type and scaling of reference 1 received
from the external controller. The resulting value is
shown by 3.11 DDCS controller ref 1.
DDCS controller ref1
type
60.60
0Type and scaling are chosen automatically according
to which reference chain (see settings Torque, Speed,
Frequency) the incoming reference is connected to. If
the reference is not connected to any chain, no scaling
is applied (as with setting Transparent).
Auto
1No scaling is applied.Auto
2Generic reference with a scaling of 100 = 1 (ie. integer
and two decimals).
Auto
3The scaling is defined by parameter 46.3 Torque scaling.Torque
4The scaling is defined by parameter 46.1 Speed scaling.Speed
5The scaling is defined by parameter 46.2 Frequency
scaling.
Frequency
Auto / uint16Selects the type and scaling of reference 2 received
from the external controller. The resulting value is
shown by 3.12 DDCS controller ref 2.
For the selections, see parameter 60.60 DDCS controller
ref1 type.
DDCS controller ref2
type
60.61
Auto / uint16Selects the type/source and scaling of actual value
ACT1 transmitted to the external controller.
DDCS controller act1
type
60.62
Parameters 503