Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0Type/source and scaling follow the type of reference
1 selected by parameter 60.60 DDCS controller ref1
type. See the individual settings below for the sources
and scalings.
Auto
1Reserved.
2Reserved.
31.10 Motor torque is sent as actual value 1. The scaling
is defined by parameter 46.3 Torque scaling.
Torque
41.1 Motor speed used is sent as actual value 1. The
scaling is defined by parameter 46.1 Speed scaling.
Speed
51.6 Output frequency is sent as actual value 1. The
scaling is defined by parameter 46.2 Frequency scaling.
Frequency
Auto / uint16Selects the type/source and scaling of actual value
ACT2 transmitted to the external controller.
DDCS controller act2
type
60.63
0Type/source and scaling follow the type of reference
2 selected by parameter 60.61 DDCS controller ref2
type. See the individual settings below for the sources
and scalings.
Auto
1Reserved.Auto
2Reserved.Auto
31.10 Motor torque is sent as actual value 2. The scaling
is defined by parameter 46.3 Torque scaling.
Torque
41.1 Motor speed used is sent as actual value 2. The
scaling is defined by parameter 46.1 Speed scaling.
Speed
51.6 Output frequency is sent as actual value 2. The
scaling is defined by parameter 46.2 Frequency scaling.
Frequency
0 / uint16Selects the pair of data sets used by the mailbox service
in the drive/controller communication.
See section External controller interface (page 81).
Mailbox dataset
selection
60.64
- / -Data sets 32 and 33.0...1
- / uint16Activates DDCS controller communication monitoring
separately for each control location (see section Local
control vs. external control (page 39).
The parameter is primarily intended for monitoring the
communication with the controller when it is connected
to the application program and not selected as a
control source by drive parameters.
DDCS controller
comm supervision
force
60.65
1 = Communication monitoring active when Ext 1 is
being used.
Ext 1b0
1 = Communication monitoring active when Ext 2 is
being used.
Ext 2b1
1 = Communication monitoring active when local
control is being used.
Localb2
Reservedb3…15
1 = 10000h…FFFFh
504 Parameters