Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0 / real32Defines custom scaling for the parameter 75.16 Ext2
pump speed ref src.
Ext2 speed ref scaler75.17
1 = 1 / 1 = 1Speed reference scalar.0...30000
0.00 Hz / real32Defines minimum production speed reference in
absolute value.
Minimum
production speed
75.18
10 = 1 Hz / 100 = 1 HzMinimum production speed.0.00 ... 598.00 Hz
50.00 Hz / real32Defines maximum production speed reference in
absolute value.
Maximum
production speed
75.19
10 = 1 Hz / 100 = 1 HzMaximum production speed.0.00 ... 598.00 Hz
30.0 s / real32Defines the time for the pump-motor to accelerate
from 0 up to the speed set in parameter 46.2 Frequency
scaling.
Note: If parameter 75.23 Ramp switch speed is set to
greater than 0, then this parameter ramp time setting
is used while speed reference is in lower speed region.
Acceleration time75.21
1 = 1 s / 10 = 1 sAcceleration time in seconds.0.0 ... 1800.0 s
30.0 s / real32Defines the time for the pump-motor to decelerate
from the speed set in parameter 46.2 Frequency scaling
down to 0.
Note: If parameter 75.23 Ramp switch speed is set to
greater than 0, then this parameter ramp time setting
is used while speed reference is in lower speed region.
Deceleration time75.22
1 = 1 s / 10 = 1 sDeceleration time in seconds.0.0 ... 1800.0 s
0.00 Hz / real32Defines the speed at which ramp time should switch
from ramp set 1 to ramp set 2.
Ramp set 1 (75.21 Acceleration time and 75.22
Deceleration time) is used in speed range from
75.15 Starting speed up to 75.23 Ramp switch
speed.
When speed reference gets higher than 75.23
Ramp switch speed, then ramp set 2 is used (75.24
Acceleration time 2 and 75.25 Deceleration time
2).
If parameter value is "0", then only ramp set 1 is
used for the complete production speed range.
Ramp switch speed75.23
10 = 1 Hz / 100 = 1 HzRamp switch speed.0.00 ... 598.00 Hz
30.0 s / real32Defines the time for the pump-motor to accelerate
from 0 up to the speed set in parameter 46.2 Frequency
scaling.
Note: If parameter 75.23 Ramp switch speed is set to
greater than 0, then this parameter ramp time setting
is used while speed reference is in lower speed region.
Acceleration time 275.24
1 = 1 s / 10 = 1 sAcceleration time 2 in seconds.0.0 ... 1800.0 s
Parameters 527