Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
12Parameter 74.1 ESP control word (page 519), bit 6 status
controls enable/disable status of the function.
ESP CW bit 6
See Terms and abbreviations (page 169).Other [bit]
4.0% / real32Defines the speed reference used to perform current
pulse-start routine. The base value to calculate the
current pulse speed reference is parameter 99.9 Motor
nominal speed.
Current pulse speed
reference
75.61
10 = 1% / 10 = 1%Current pulse speed reference.0.0 ... 100.0%
100.0% / real32Defines the motor current reference used for producing
a thrust to the pump impeller.
This is active only for the time defined with parameter
75.69 Current pulse cycle time. This can be repeated as
many times as set in parameter 75.68 Current pulse nr
of cycles.
The base value to calculate the current pulse start
reference is parameter 99.6 Motor nominal current.
Current pulse start
current ref
75.62
10 = 1% / 10 = 1%Current pulse start current ref.0.0 ... 300.0%
- / real32Defines the quantity of desired current pulses applied
in sequence.
Each cycle consists of a period of thrust generated by
high motor current set in parameter 75.62 Current pulse
start current ref and a period of waiting together
lasting as long as set in parameter 75.69 Current pulse
cycle time.
Current pulse nr of
cycles
75.68
1 = 1 / 1 = 1Current pulse number of cycles.0...30000
1.0 s / real32Defines the time for a period in the current pulse-start
routine.
Each cycle consists of two such periods.
Current pulse cycle
time
75.69
10 = 1 s / 10 = 1 sCurrent pulse cycle time.0.0 ... 30000.0 s
0.00 Hz / real32Defines the pump speed reference.
This parameter is read-only.
Pump speed ref in75.81
10 = 1 Hz / 100 = 1 HzPump speed reference.0.00 ... 598.00 Hz
- / unit16Displays the status word of the functions controlling
ESP control program starting routines, i.e. Starting
speed, Acceleration assistance, Kick-start and Current
pulse-start.
Starting routines75.99