Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
5.0 s / real32Defines safe motor speed ramp setting used when
automatic process control mode is active.
In order to prevent undesired speed steps due to
process feedback signal errors or any other reason, it
is recommended to set this parameter value as high
as it seems reasonable it terms of expected speed
change dynamics.
Auto mode motor
ramp time
76.19
10 = 1 s / 1 = 1 sAuto mode motor ramp time.0.0 ... 30000.0 s
Off / unit32Selects the source to invert process PI controller error
sign.
Invert PI error sign76.29
0Invert process controller error sign is inactive.Off
1Inverts both Process1 and Process 2.Invert both
2Invert process 1 control error sign.Invert process 1
3Invert process 2 control error sign.Invert process 2
Estimated flowrate /
unit16
Defines the source for the process 1 feedback signal.Process 1 control
feedback src
76.31
0NoneNULL
112.12 AI1 scaled value (page 226).AI1 scaled
212.22 AI2 scaled value (page 228).AI1 scaled
43.5 FB A reference 1 (page 179).FB A1 ref
53.6 FB A reference 2 (page 179).FB A2 ref
83.9 EFB reference 1 (page 179).EFB ref1
93.10 EFB reference 2 (page 179).EFB ref2
7Parameter 9.13 Motor current estimated.Estimated current
8Estimated motor current in % of nominal motor current.Motor current %
9Signal
85.91 Flowrate actual
is used as the process
feedback source.
Estimated flowrate
10Signal
85.92 Head actual
is used as the process
feedback source.
Estimated head
See Terms and abbreviations (page 169).Other [bit]
0.00 / real32Defines the value for the process 1 reference set point.Process 1 control set
point
76.33
100 = 1 / 10 = 1Process 1 control set point.0.00 ... 3000000.00
1000.0 / real32Defines the value for the process 1 feedback and
reference unit scaling.
It is assumed that the process signal might change in
range from 0 to a value set in this parameter. This
setting only serves for rendering process unit to the
percent scale and does not limit the input in any way.
Note: When this parameter is set to 0, the process 1
feedback and set point reference scaling is bypassed.
The values are then taken to the process PI controller
input.
Process 1 max scale76.35
Parameters 533