Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
10.0 s / real32Defines the time used as on-delay for the overload
protection function to react to the overload condition.
Overload delay time79.48
1 = 1 s / 10 = 1 sOverload delay time in seconds.0.0 ... 30000.0 s
Warning / unit32Defines the response to the overload condition.
If the overload supervision signal is above active
overload limit in the defined delay time, then overload
protection function trigger the reaction defined in this
parameter setting.
Overload event
reaction
79.49
0Overload event reaction is inactive.Not selected
1Overload condition triggers the drive event D208
Overload warning. It will stay on as long as overload
condition is present. The warning will automatically
disappear if overload supervision signal stays below
the overload limit for the time defined in parameter
79.48 Overload delay time.
Warning
2Overload condition triggers the drive event D208
Overload warning and immediate stop command. Drive
will stop according to parameter 21.3 Stop mode
setting.
Warning with
shutdown
3Overload condition triggers the drive event D101
Overload fault which immediately trips the drive.
Fault
4Overload condition triggers the overload recovery
sequence.
In case recovery routine helps, the motor speed returns
to production speed. If not, drive generates the event
D208 Overload warning. It will stay on as long as
overload condition is present. The warning will
automatically disappear if overload supervision signal
stays below the overload limit for the time defined in
parameter 79.48 Overload delay time.
Recovery - warning
5Overload condition triggers the overload recovery
sequence.
In case recovery routine helps, motor speed returns to
production speed. If not, drive generates the event
D101 Overload fault which immediately trips the drive.
Recovery - Fault
0.00 / real32Defines overload curve point 1 load limit active at
corresponding speed set in parameter 79.01 Load curve
speed point 1.
Overload curve point
1
79.51
10 = 1 / 100 = 1Overload curve point 1.-30000.00 ...
30000.00
0.00 / real32Defines overload curve point 2 load limit active at
corresponding speed set in parameter 79.02 Load curve
speed point 2.
Overload curve point
2
79.52
10 = 1 / 100 = 1Overload curve point 2.-30000.00 ...
30000.00
0.00 / real32Defines overload curve point 3 load limit active at
corresponding speed set in parameter 79.03 Load curve
speed point 3.
Overload curve point
3
79.53
Parameters 543