Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1 = 1 s / 100 = 1 sCleaning deceleration time in seconds.0.00 ... 30000.00 s
100.00% / real32Defines the motor current reference setting used
during acceleration period of every cleaning cycle.
This helps to produce higher starting torque and assist
acceleration.
Note: For the Acceleration boost to work, parameter
81.02 Pump cleaning option sel, bit-7 must be set to 1.
Acceleration boost
current
81.35
10 = 1% / 100 = 1%Acceleration boost current.0.00 ... 300.00%
Not selected / unit32Defines source for the cleaning abort command.
The cleaning operation can be interrupted at any time
with abort command. In such case, ESP control program
will immediately switch to production mode.
Cleaning abort
source
81.40
0Cleaning abort source is not selected.Not selected
1Cleaning abort source is selected.Selected
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
See Terms and abbreviations (page 169).Other [bit]
Motor current % /
unit32
Defines the source for the supervision low signal.
The value from this parameter is then compared with
the limit set in parameter 81.42 Supervision low limit.
If the observed signal is lower than the limit for the
time period set in parameter 81.43 Supervision low
delay, then cleaning procedure is interrupted. The ESP
control program will immediately switch to production
mode. The supervision low is not active during off-time
period.
Note: For the supervision low function to work,
parameter 81.02 Pump cleaning option sel bit-11 must
be set to 1.
Supervision low
signal src
81.41
0ZeroNULL
112.12 AI1 scaled value (page 226).AI1 scaled
212.22 AI2 scaled value (page 228).AI2 scaled
33.5 FB A reference 1 (page 179).FBA1 ref
43.6 FB A reference 2 (page 179).FBA2 ref
53.9 EFB reference 1 (page 179).EFB1 ref
Parameters 555