EasyManua.ls Logo

ABB ACS880 - Page 556

ABB ACS880
764 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
63.10 EFB reference 2 (page 179).EFB2 ref
7Parameter 9.13 Motor current estimated (page 209).Estimated motor
current
8Estimated motor current in % of nominal motor current.Motor current %
See Terms and abbreviations (page 169).Other [value]
0.00 / real32Defines low limit value for the Supervision low function.
See parameter 81.41 Supervision low signal src.
Supervision low limit81.42
10 = 1 / 100 = 1Supervision low limit.0.00 ... 30000.00
10.0 s / real32Defines delay time for the Supervision low function.
See parameter 81.41 Supervision low signal src.
Supervision low
delay
81.43
10 = 1 s / 10 = 1 sSupervision low delay.0.0 ... 3200.0 s
Motor current % /
unit32
Defines the source for the supervision high signal.
The value of this parameter is then compared with the
limit set in parameter 81.47 Supervision high limit.
If the observed signal is greater than the limit for the
time period set in parameter 81.48 Supervision high
delay, then the current cleaning step is interrupted.
Cleaning sequence will proceed for the off-time and
then switch to the next cleaning step. The supervision
high is not active during the off-time period.
Note: For the Supervision High function to work,
parameter 81.02 Pump cleaning option sel, bit-12 must
be set to 1.
Supervision high
signal src
81.46
0ZeroNULL
112.12 AI1 scaled value (page 226).AI1 scaled
212.22 AI2 scaled value (page 228).AI2 scaled
33.5 FB A reference 1 (page 179).FBA1 ref
43.6 FB A reference 2 (page 179).FBA2 ref
53.9 EFB reference 1 (page 179).EFB1 ref
63.10 EFB reference 2 (page 179).EFB2 ref
7Parameter 9.13 Motor current estimated (page 209).Estimated motor
current
8Estimated motor current in % of nominal motor current.Motor current %
See Terms and abbreviations (page 169).Other [value]
0.00 / real32Defines low limit value for the Supervision high
function.
See parameter 81.46 Supervision high signal src.
Supervision high
limit
81.47
10 = 1 / 100 = 1Supervision high limit.0.00 ... 30000.00
10.0 s / real32Defines delay time for the Supervision high function.
See parameter 81.46 Supervision high signal src.
Supervision high
delay
81.48
10 = 1 s / 10 = 1 sSupervision high delay.0.0 ... 3200.0 s
556 Parameters