EasyManua.ls Logo

ABB ACS880 - Page 557

ABB ACS880
764 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Not selected / unit32Defines the control program response event type in
case the actual amount of cleaning operation exceeds
the defined limit set in parameter 81.52 Clean max
amount in period of time set in parameter 81.53 Clean
max period.
Cleaning max event81.51
0Cleaning maximum event is not selected.Not selected
1Cleaning maximum event generates a warning.Warning
2Cleaning maximum event generates a fault.Fault
- / real32Defines maximum allowed quantity of cleaning
operations in time period set in parameter 81.53 Clean
max period.
Clean max amount81.52
1 = 1 / 1 = 1Maximum cleaning amount.0...100
0.00 hour / real32Defines the time window span for the function which
monitors the number of cleaning operations.
Clean max period81.53
100 = 1 hour / 100 = 1
hour
Cleaning maximum period in hours.0.00 ... 650.00 hour
0.00% / real32Displays active speed reference from the cleaning
function.
Cleaning reference
%
81.80
10 = 1% / 100 = 1%Cleaning reference.-1200.00 ...
1200.00%
- / real32Displays the time elapsed since last cleaning operation
was completed.
Since last cleaning81.81
- / 1Elapsed time since last cleaning.00:00:00...99:00:00
- / real32Displays the time remaining before next cleaning
request is initiated by the Time trigger function.
Until next cleaning81.82
- / 1Until next cleaning.00:00:00...99:00:00
- / unit16Displays status word for the pump cleaning function.Cleaning status
word
81.99
Cleaning operation is active.Cleaning startedb0
Cleaning request is issued. Cleaning will be performed
on the next drive start.
Cleaning requestedb1
Enables starting speed. See parameter 75.15 Starting
speed.
First stepb2
Off step is active.Off stepb3
Second step is active.Second stepb4
Cleaning procedure has been completed on last start.Cleaning doneb5
Cleaning aborted by the low/high supervision.Aborted by
supervision
b6
Cleaning acceleration boost active.Acceleration boost
act
b7
Reservedb8...10
Cleaning requested from the manual trigger source.Requested by
manual trigger
b11
Parameters 557

Table of Contents

Other manuals for ABB ACS880

Related product manuals