Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / real32Displays the temperature measured through the sensor
input of interface module 2. The unit (°C or °F) is
selected by parameter 96.16 Unit selection.
Note: With a PTC sensor, the unit is ohms.
Note: This parameter is read-only.
Module 2
temperature
91.6
- / -Temperature measured through interface module 2.0.0 ... 1000.0 °C
Done / uint16Validates any changed encoder interface module
parameters. This is needed for any parameter changes
in groups 90…93 to take effect.
After refreshing, the value reverts automatically to
Done.
• Permanent magnet motors only: The drive will
perform a fresh autophasing routine (see page
102) at next start if the motor feedback encoder
settings have been changed.
• The parameter cannot be changed while the drive
is running.
Encoder parameter
refresh
91.10
0Refreshing done.Done
1Refreshing.Refresh
None / uint16Defines the type of the module used as interface
module 1.
Module 1 type91.11
0None (communication disabled).None
1FEN-01.FEN-01
2FEN-11.FEN-11
3FEN-21.FEN-21
4FEN-31.FEN-31
5FSE-31.FSE-31
2 / uint16Specifies the slot (1…3) on the control unit of the drive
into which the interface module is installed.
Alternatively, specifies the node ID of the slot on an
FEA-03 extension adapter.
Module 1 location91.12
1 = 1 / 1 = 1Slot 1 = 1; Slot 2 = 2; Slot 3 = 3
4…254: Node ID of the slot on the FEA-03 extension
adapter
1...254
None / uint16Defines the type of the module used as interface
module 2.
Module 2 type91.13
0None (communication disabled).None
1FEN-01.FEN-01
2FEN-11.FEN-11
3FEN-21.FEN-21
4FEN-31.FEN-31
5FSE-31.FSE-31
Parameters 577