Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / real32
(Only visible when IGBT supply unit control activated
by
95.20
)
Displays the reactive power reference sent to the supply
unit.
Note: This parameter is read-only.
Reactive power
reference
94.30
10 = 1 kVAr / 10 = 1
kVAr
Reactive power reference sent to the supply unit.-3276.8 ... 3276.7
kVAr
User ref / uint32
(Only visible when IGBT supply unit control activated
by
95.20
)
Selects the source of the reactive power reference to
be sent to the supply unit.
Reactive power ref
source
94.31
0None.Zero
194.32 User reactive power reference.User ref
See Terms and abbreviations (page 169).Other [value]
0.0 kVAr / real32
(Only visible when IGBT supply unit control activated
by
95.20
)
Defines the reactive power reference for the supply
unit when 94.31 Reactive power ref source is set to User
ref.
User reactive power
reference
94.32
10 = 1 kVAr / 10 = 1
kVAr
User reactive power reference.-3276.8 ... 3276.7
kVAr
600.00 % / real32Defines the maximum shaft power for motoring mode
upon a supply network failure when IGBT supply unit
control is active (bit 15 of 95.20 HW options word 1 is
on).
The value is given in percent of nominal motor power.
Note: With a diode supply unit (bit 11 of 95.20 is on),
the motoring shaft power is limited to 2% upon a
network failure regardless of this parameter.
Power mot limit on
net loss
94.40
1 = 1 % / 100 = 1 %Maximum shaft power for motoring mode upon a
supply network failure.
0.00 ... 600.00 %
-600.00 % / real32Defines the maximum shaft power for generating upon
a supply network failure when supply unit control is
active (bit 15 of 95.20 HW options word 1 is on).
The value is given in percent of nominal motor power.
Note: With a diode supply unit (bit 11 of 95.20 is on),
the motoring shaft power is limited to 2% upon a
network failure regardless of this parameter.
Power gen limit on
net loss
94.41
1 = 1 % / 100 = 1 %Maximum shaft power for generating mode upon a
supply network failure.
-600.00 ... 0.00 %
Parameters 591