Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1Factory macro (see 150).Factory
2Hand/Auto macro (see page 152).Hand/Auto
3PID control macro (see page 155).PID-CTRL
4Torque control macro (see page 160).T-CTRL
5Sequential control macro (see page 163).Sequence control
6Reserved.
Factory / uint16Shows which application macro is currently selected.
To change the macro, use parameter 96.4 Macro select.
Macro active96.5
1Factory macro (see 150).Factory
2Hand/Auto macro (see page 152).Hand/Auto
3PID control macro (see page 155).PID-CTRL
4Torque control macro (see page 160).T-CTRL
5Sequential control macro (see page 163).Sequence control
6Reserved.
Done / uint16Restores the original settings of the control program,
i.e. parameter default values.
Note: This parameter cannot be changed while the
drive is running.
Parameter restore96.6
0Restoring is completed.Done
8All editable parameter values are restored to default
values, except
motor data and ID run results
parameter 31.42 Overcurrent fault limit
control panel/PC communication settings
I/O extension module settings
fieldbus adapter settings
encoder configuration data
application macro selection and the parameter
defaults implemented by it
parameter 95.21 HW options word 2
parameter 95.9 Switch fuse controller
differentiated defaults implemented by
parameters 95.20 HW options word 1 and 95.21
HW options word 2
user lock configuration parameters
96.100 96.102.
Restore defaults
604 Parameters