Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
62All editable parameter values are restored to default
values, except
• control panel/PC communication settings
• application macro selection and the parameter
defaults implemented by it
• parameter 95.1 Supply voltage
• parameter 95.9 Switch fuse controller
• differentiated defaults implemented by
parameters 95.20 HW options word 1 and 95.21
HW options word 2
• user lock configuration parameters
96.100 … 96.102.
PC tool communication is interrupted during the
restoring.
Note: Activating this selection will restore the default
settings of the fieldbus adapter if one is connected,
potentially including settings that cannot be accessed
through drive parameters.
Clear all
32Fieldbus adapter and embedded fieldbus interface
settings (parameter groups 50…58) are restored to
default values. This will also restore the default settings
of the fieldbus adapter if one is connected, potentially
including settings that cannot be accessed through
drive parameters.
Reset all fieldbus
settings
Done / uint16Saves the valid parameter values to permanent memory.
This parameter should be used to store values sent
from a fieldbus, or when using an external power supply
to the control board as the supply might have a very
short hold-up time when powered off.
Note: A new parameter value is saved automatically
when changed from the PC tool or control panel but
not when altered through a fieldbus adapter
connection.
Parameter save
manually
96.7
0Save completed.Done
1Start save, or save in progress.Save
- / uint16Changing the value of this parameter to 1 reboots the
control unit (without requiring a power off/on cycle of
the complete drive module).
The value reverts to 0 automatically.
Note: This parameter cannot be changed while the
drive is running.
Control board boot96.8
1 = 1 / 1 = 11 = Reboot the control unit.0...1
Parameters 605