Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1 = 1st priority tick received: Tick has been received
from 1st priority source (or from 96.24 96.26).
Time tick receivedb0
1 = 2nd priority tick received: Tick has been received
from 2nd priority source.
Aux Time tick
received
b1
1 = Yes: Tick interval too long (accuracy compromised).Tick interval is too
long
b2
1 = Tick received: Tick has been received from an
external controller.
DDCS controllerb3
1 = Tick received: Tick has been received through the
master/follower link.
Master/Followerb4
Reservedb5
1 = Tick received: Tick has been received through the
drive-to-drive link.
D2Db6
1 = Tick received: Tick has been received through
fieldbus interface A.
FbusAb7
1 = Tick received: Tick has been received through
fieldbus interface B.
FbusBb8
1 = Tick received: Tick has been received through the
embedded fieldbus interface.
EFBb9
Reservedb10
1 = Tick received: Tick has been received from the
control panel, or Drive Composer PC tool connected to
the control panel.
Panel linkb11
1 = Tick received: Tick has been received from Drive
Composer PC tool through an FENA module.
Ethernet tool linkb12
1 = Tick received: Tick has been set by parameters
96.24 96.26.
Parameter settingb13
1 = RTC time in use: Time and date have been read from
the real-time clock.
RTCb14
1 = Drive on-time in use: Time and date are displaying
drive on-time.
Drive On-Timeb15
1 = 10000h…FFFFh
0 / uint16Specifies an ID number for the drive. The ID can be read
by an external controller through DDCS, for example,
for comparison with an ID contained by the controller's
application.
Drive ID number96.31
1 = 1 / 1 = 1ID number.0...32767
Enable / uint16Enables/disables power-up logging. When enabled, an
event (B5A2 Power up) is logged by the drive upon each
power-up.
Power up event
logging
96.39
0Power-up event logging disabled.Disable
1Power-up event logging enabled.Enable
- / uint16Clears the contents of the event logs. See section
Warning/fault history and analysis (page 650).
Clear fault and event
logger
96.51
Parameters 609