Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
500500 microseconds.500us
20002 milliseconds.2ms
1000010 milliseconds.10ms
No / uint16Disables/enables the adaptive program (if present).
See also section Adaptive programming (page 69).
Note: This parameter cannot be changed while the
drive is running.
Disable adaptive
program
96.70
0Adaptive program enabled.No
1Adaptive program disabled.Yes
10000000 / uint32
(Visible when user lock is open)
To change the current user pass code, enter a new code
into this parameter as well as 96.101 Confirm user pass
code. A warning will be active until the new pass code
is confirmed. To cancel changing the pass code, close
the user lock without confirming. To close the lock,
enter an invalid pass code in parameter 96.2 Pass code,
activate parameter 96.8 Control board boot, or cycle
the power.
See also section User lock (page 142).
Change user pass
code
96.100
1 = 1New user pass code.10000000…99999999
10000000 / uint32
(Visible when user lock is open)
Confirms the new user pass code entered in 96.100
Change user pass code (page 612).
Confirm user pass
code
96.101
1 = 1Confirmation of new user pass code.10000000…99999999
- / uint16
(Visible when user lock is open)
Selects the actions or functionalities to be prevented
by the user lock. Note that the changes made take
effect only when the user lock is closed. See parameter
96.2 Pass code.
Note: We recommend you select all the actions and
functionalities unless otherwise required by the
application.
User lock
functionality
96.102
1 = ABB access levels (service, advanced programmer,
etc. [see 96.3]) disabled
Disable ABB access
levels
b0
1 = Changing the parameter lock state prevented, ie.
pass code 358 has no effect
Freeze parameter
lock state
b1
612 Parameters