Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1 = Loading of files to drive prevented. This applies to
firmware upgrades
safety functions module (FSO-xx) configuration
parameter restore
loading an adaptive program
loading and debugging an application program
changing home view of control panel
editing drive texts
editing the favorite parameters list on control
panel
configuration settings made through control panel
such as time/date formats and enabling/disabling
clock display.
Disable file
download
b2
1 = Access to parameters on disabled access levels from
fieldbus prevented
Disable FB write to
hidden
b3
Reservedb4…5
1 = Creating a backup and restoring from a backup
prevented
Protect APb6
1 = Bluetooth disabled on ACS-AP-W control panel. If
the drive is part of a panel bus, Bluetooth is disabled
on all panels.
Disable panel
bluetooth
b7
Reservedb8…10
1 = OEM access level 1 disabledDisable OEM access
level 1
b11
1 = OEM access level 2 disabledDisable OEM access
level 2
b12
1 = OEM access level 3 disabledDisable OEM access
level 3
b13
Reservedb14…15
1 = 10000h…FFFFh
0 / uint16
(Visible when IGBT supply unit control activated by
95.20
)
Changing the value of this parameter to 1 reboots the
supply control unit (without requiring a power off/on
cycle of the drive system). The value reverts to 0
automatically.
LSU control board
boot
96.108
1 = 1 / 1 = 11 = Reboot the supply control unit.0...1