Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
2Control performance optimized for cyclic load
applications.
Cyclic
3This setting is to be used by ABB-authorized service
personnel only.
Custom
Disabled / uint16Enables signal injection. A high-frequency alternating
signal is injected into the motor at low speeds to
improve the stability of torque control. Signal injection
can be enabled with different amplitude levels.
Note: This is an expert level parameter and should not
be adjusted without appropriate skill.
Note: Use as low a level as possible that gives
satisfactory performance.
Note: Signal injection cannot be applied to
asynchronous motors.
Signal injection97.10
0Signal injection disabled.Disabled
1Signal injection enabled with an amplitude level of 5%.Enabled (5 %)
2Signal injection enabled with an amplitude level of 10%.Enabled (10 %)
3Signal injection enabled with an amplitude level of 15%.Enabled (15 %)
4Signal injection enabled with an amplitude level of 20%.Enabled (20 %)
100 % / real32Rotor time constant tuning.
This parameter can be used to improve torque accuracy
in closed-loop control of an induction motor. Normally,
the motor identification run provides sufficient torque
accuracy, but manual fine-tuning can be applied in
exceptionally demanding applications to achieve
optimal performance.
Note: This is an expert level parameter and should not
be adjusted without appropriate skill.
TR tuning97.11
1 = 1 % / 100 = 1 %Rotor time constant tuning.25...400 %
Disabled / uint16Selects whether the temperature-dependent
parameters (such as stator or rotor resistance) of the
motor model adapt to actual (measured or estimated)
temperature or not.
See parameter group 35 Motor thermal protection for
selection of temperature measurement sources.
Motor model
temperature
adaptation
97.15
0Temperature adaptation of motor model disabled.Disabled
1Estimated temperature (35.1 Motor estimated
temperature) used for adaptation of motor model.
Estimated
temperature
2Measured temperature 1 (35.2 Measured temperature
1) used for adaptation of motor model.
Measured
temperature 1
3Measured temperature 2 (35.3 Measured temperature
2) used for adaptation of motor model.
Measured
temperature 2
616 Parameters