EasyManua.ls Logo

ABB ACS880 - Page 629

ABB ACS880
764 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0.00 uF / real32Defines the capacitance of a custom sine filter, i.e. when
parameter 95.15 Special HW settings bit 3 is activated.
If the capacitors are star/wye-connected, enter the
capacitance of one leg into the parameter.
M
3~
C
99.19 = C
C C
Drive
Sine filter
If the capacitors are delta-connected, multiply the
capacitance of one leg by 3 and enter the result into
the parameter.
M
3~
CC
C
99.19 = 3 × C
Drive
Sine filter
Note: For an ABB sine filter (95.15 Special HW settings
bit 1), this parameter is set automatically and should
not be adjusted.
Sine filter
capacitance
99.19
100 = 1 uF / 100 = 1
uF
Capacitance of custom sine filter.0.00 ... 100000.00 uF
Done / uint16Selects the option to calculate the required low voltage
side data.
Note: All ESP circuitry related parameters (listed below)
must be updated before this calculation.
Parameters:
95.01, 95.40, 95.200 (if known), 95.201,
95.202...95.204 (if known)
99.18, 99.19, 99.201...99.207
Med-voltage side
data
99.200
0Requested action is completed. No more action
required.
Done
1Low voltage side data is calculated using the medium
voltage side data.
Calculate and apply
0.0 A / real32Defines nominal current of the ESP motor. This setting
must match the value on the rating plate of the motor.
ESP motor nominal
current
99.201
10 = 1 A / 10 = 1 ANominal current of the ESP motor.0.0 ... 6400.0 A