Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Distributed I/O bus settings.I/O bus service207
This group is only visible with a BCU control unit.
This group contain parameters related to the
distributed I/O bus, which is used with some drives for
monitoring the cooling fans of the cabinet system. For
details, refer to
CIO-01 I/O module for distributed I/O
bus control user’s manual
(3AXD50000126880
[English]).
1 / uint16Selects the node. Note: All the parameters in this
parameter group concern the selected node only.
Node ID number207.1
1 / 1Node ID number.1...99
- / uint16Selects the fan(s) for the operation selected with
parameter 207.03 Command selection.
Fan reset selection207.2
1 = Fan 1 in the selected node.b0
1 = Fan 2 in the selected node.b1
1 = Fan 3 in the selected node.b2
1 = Fan 4 in the selected node.b3
Reservedb4…15
1 = 10000h…FFFFh
None / uint16Selects the operation for the fan(s) selected with
parameter 207.02 Fan reset selection.
Command selection207.3
0None.
1Shows the operating time (in hours) of the fan(s) in
parameters 207.11…207.14.
2Resets the on-time counter of the fan(s).
3Resets the last identification run of the fan(s).
4Resets the on-time counter and identification run data
shown by parameters 207.11…207.14. Can be used if a
fan is replaced with a new one.
5Shows the speeds (in Hz) of the fan(s) in parameters
207.11…207.14.
Done / uint16Performs the operation selected with parameter 207.03
Command selection.
Service request
trigger
207.10
0Operation done or not requested.
1Performs the operation.
- / real32Shows the output of the operation selected with
parameter 207.03 Command selection for fan 1.
Fan 1 data207.11
1 / 100Fan 1 data.0.00 ...
2147483640.00
- / real32Shows the output of the operation selected with
parameter 207.03 Command selection for fan 2.
Fan 2 data207.12
1 / 100Fan 2 data.0.00 ...
2147483640.00