What to doCause
Event name /
Aux. code
Code
(hex)
Check the settings of the motor
configuration parameters in groups
98 and 99.
Nominal current is outside limits.4
Check that the drive is sized
correctly for the motor.
Check the settings of the motor
configuration parameters in groups
98 and 99.
Nominal voltage is outside limits.5
Check that the drive is sized
correctly for the motor.
Check the settings of the motor
configuration parameters in groups
98 and 99.
Mechanical nominal power is higher
than electrical active power.
6
Check that the drive is sized
correctly for the motor.
Check the settings of the motor
configuration parameters in groups
98 and 99.
Nominal power not consistent with
nominal speed and torque.
7
Check that the drive is sized
correctly for the motor.
Check that all the required parameters
in group 99 have been set.
Parameters in group 99 have not been
set.
No motor
data
A6A5
Note: It is normal for this warning to
appear during the start-up and
continue until the motor data is
entered.
Set supply voltage in parameter 95.1
Supply voltage.
The supply voltage has not been
defined.
Supply
voltage
unselected
A6A6
Close the user lock by entering an
invalid pass code in parameter 96.2
The user lock is open, ie. user lock
configuration parameters
96.100…96.102 are visible.
User lock
open
A6B0
Pass code. See section User
lock (page 142).
Confirm the new pass code by
entering the same code in 96.101. To
A new user pass code has been
entered in parameter 96.100 but not
confirmed in 96.101.
User pass
code not
confirmed
A6B1
cancel, close the user lock without
confirming the new code. See section
User lock (page 142).
Check PLC programming.The drive does not have a functionality
requested by a PLC, or requested
functionality has not been activated.
FBA A
parameter
conflict
A6D1
Check settings of parameter groups
50 Fieldbus adapter (FBA) and 51 FBA
A settings.
Check PLC programming.The drive does not have a functionality
requested by a PLC, or requested
functionality has not been activated.
FBA B
Parameter
conflict
A6D2
Check settings of parameter groups
50 Fieldbus adapter (FBA) and 54 FBA
B settings.
Check the reference source selection
parameters.
A reference source is simultaneously
connected to multiple parameters
with different units.
Reference
source
parametrization
A6DA
Check the auxiliary code (format XXYY
00ZZ). “XX” and “YY” specify the two
678 Fault tracing