What to doCause
Event name /
Aux. code
Code
(hex)
If the encoder was working
previously, check the encoder,
encoder cable and encoder interface
module for damage.
See also parameter 92.21 Encoder
cable fault mode.
Check the condition of the encoder.No encoder signal.0002
Contact your local ABB
representative.
Overspeed.0003
Contact your local ABB
representative.
Overfrequency.0004
Contact your local ABB
representative.
Resolver ID run failed.0005
Contact your local ABB
representative.
Resolver overcurrent fault.0006
Contact your local ABB
representative.
Speed scaling error.0007
Contact your local ABB
representative.
Absolute encoder communication
error.
0008
Contact your local ABB
representative.
Absolute encoder initialization error.0009
Contact your local ABB
representative.
Absolute SSI encoder configuration
error.
000A
See the documentation of the
encoder.
Encoder reported an internal error.000B
See the documentation of the
encoder.
Encoder reported a battery error.000C
See the documentation of the
encoder.
Encoder reported overspeed or
decreased resolution due to
overspeed.
000D
See the documentation of the
encoder.
Encoder reported a position counter
error.
000E
See the documentation of the
encoder.
Encoder reported an internal error.000F
Check PC tool or control panel
connection.
Control panel (or PC tool) has stopped
communicating.
Control panel
loss
A7EE
Check control panel connector.
Check mounting platform if being
used.
Disconnect and reconnect the control
panel.
Check the auxiliary code. Check the
source of the warning corresponding
to the code:
Warning generated by an ontime timer
or a value counter.
Motor bearingA880
0: 33.13 On-time 1 source
1: 33.23 On-time 2 source
4: 33.53 Value counter 1 source
5: 33.63 Value counter 2 source.
Check the auxiliary code. Check the
source of the warning corresponding
to the code:
Warning generated by an edge
counter.
Programmable warnings:
Output relayA881