What to doCause
Event name /
Aux. code
Code
(hex)
2: 33.33 Edge counter 1 source33.35 Edge counter 1 warn message
3: 33.43 Edge counter 2 source.33.45 Edge counter 2 warn message
Check the auxiliary code. Check the
source of the warning corresponding
to the code:
Warning generated by an edge
counter.
Programmable warnings:
Motor startsA882
2: 33.33 Edge counter 1 source33.35 Edge counter 1 warn message
3: 33.43 Edge counter 2 source.33.45 Edge counter 2 warn message
Check the auxiliary code. Check the
source of the warning corresponding
to the code:
Warning generated by an edge
counter.
Programmable warnings:
Power upsA883
2: 33.33 Edge counter 1 source33.35 Edge counter 1 warn message
3: 33.43 Edge counter 2 source.33.45 Edge counter 2 warn message
Check the auxiliary code. Check the
source of the warning corresponding
to the code:
Warning generated by an edge
counter.
Programmable warnings:
Main
contactor
A884
2: 33.33 Edge counter 1 source33.35 Edge counter 1 warn message
3: 33.43 Edge counter 2 source.33.45 Edge counter 2 warn message
Check the auxiliary code. Check the
source of the warning corresponding
to the code:
Warning generated by an edge
counter.
Programmable warnings:
DC chargeA885
2: 33.33 Edge counter 1 source33.35 Edge counter 1 warn message
3: 33.43 Edge counter 2 source.33.45 Edge counter 2 warn message
Check the source of the warning
(parameter 33.13 On-time 1 source).
Warning generated by on-time timer
1.
On-Time 1A886
Check the source of the warning
(parameter 33.23 On-time 2 source).
Warning generated by on-time timer
2.
On-Time 2A887
Check the source of the warning
(parameter 33.33 Edge counter 1
source).
Warning generated by edge counter 1.Edge counter
1
A888
Check the source of the warning
(parameter 33.43 Edge counter 2
source).
Warning generated by edge counter
2.
Edge counter
2
A889
Check the source of the warning
(parameter 33.53 Value counter 1
source).
Warning generated by value counter
1.
Value counter
1
A88A
Check the source of the warning
(parameter 33.63 Value counter 2
source).
Warning generated by value counter
2.
Value counter
2
A88B
Check the auxiliary code. Check the
source of the warning corresponding
to the code:
Warning generated by an ontime
timer.
Programmable warnings:
Device cleanA88C
0: 33.13 On-time 1 source33.14 On-time 1 warn message
1: 33.23 On-time 2 source33.24 On-time 2 warn message
10: 5.4 Main fan on-time counter.
Check the auxiliary code. Check the
source of the warning corresponding
to the code:
Warning generated by an ontime
timer.
Programmable warnings:
DC capacitorA88D
0: 33.13 On-time 1 source33.14 On-time 1 warn message
1: 33.23 On-time 2 source33.24 On-time 2 warn message
10: 5.4 Main fan on-time counter.
Fault tracing 687