What to doCause
Event name /
Aux. code
Code
(hex)
Check the source of the fault
(parameter 32.217 Supervision 5
signal).
Fault generated by the signal
supervision 6 function.
Signal
supervision 3
D105
Check the source of the fault
(parameter 32.237 Supervision 7
signal).
Fault generated by the signal
supervision 7 function.
Signal
supervision 3
D106
Check the following parameters:One or more of the sync loss
conditions is fulfilled.
Out of syncD113
31.203 Sync loss sample period
31.204 Sync loss cos phi filter
time
31.205 Sync loss cos phi drop
31.206 Sync loss cos phi minimum
level
Check motor and motor cables.Maximum number of cleaning in the
defined time frame has been
exceeded.
Cleaning max
warning
D200
Check parameters 81.51 Cleaning max
event to 81.53 Clean max period for
clean maximum protection settings.
Check the source of the warning
(parameter 32.207 Supervision 4
signal).
Warning generated by the signal
supervision 4 function.
Signal
supervision 3
D20B
Check the source of the warning
(parameter 32.217 Supervision 5
signal).
Warning generated by the signal
supervision 5 function.
Signal
supervision 3
D20C
Check the source of the warning
(parameter 32.227 Supervision 6
signal).
Warning generated by the signal
supervision 6 function.
Signal
supervision 3
D20D
Check the source of the warning
(parameter 32.237 Supervision 7
signal).
Warning generated by the signal
supervision 7 function.
Signal
supervision 3
D20E
Check the following parameters:One or more of the sync loss
conditions is fulfilled.
Out of syncD213
31.203 Sync loss sample period
31.204 Sync loss cos phi filter
time
31.205 Sync loss cos phi drop
31.206 Sync loss cos phi minimum
level
Check safety circuit connections. For
more information, see appropriate
Safe torque off function is active, ie.
STO circuit 1 is broken.
Safe torque
off 1 loss
FA81
drive hardware manual and
description of parameter 31.22 STO
indication run/stop (page 370).
Check the auxiliary code, The code
contains location information,
especially with parallel-connected
inverter modules.
692 Fault tracing