STATE/DescriptionValueNameBit
Continue operation (OFF3 inactive).1OFF3_ CONTROL2
Emergency stop, stop within time defined by drive
parameter. Proceed to OFF3 ACTIVE; proceed to
SWITCH-ON INHIBITED.
0
WARNING!
Ensure that the motor and driven machine
can be stopped using this stop mode.
Proceed to OPERATION ENABLED.1INHIBIT_ OPERATION3
Note: Run enable signal must be active; see the
drive documentation. If the drive is set to receive
the Run enable signal from the fieldbus, this bit
activates the signal.
Inhibit operation. Proceed to OPERATION INHIB-
ITED.
0
Normal operation. Proceed to RAMP FUNCTION
GENERATOR: OUTPUT ENABLED.
1RAMP_OUT_ ZERO4
Force Ramp Function Generator output to zero.
Drive ramps to stop (current and DC voltage limits
in force).
0
Enable ramp function.1RAMP_HOLD5
Proceed to RAMP FUNCTION GENERATOR: ACCEL-
ERATOR ENABLED.
Halt ramping (Ramp Function Generator output
held).
0
Normal operation. Proceed to OPERATING.1RAMP_IN_ ZERO6
Note: This bit is effective only if the fieldbus inter-
face is set as the source for this signal by drive
parameters.
Force Ramp Function Generator input to zero.0
Fault reset if an active fault exists. Proceed to
SWITCH-ON INHIBITED.
0=>1RESET7
Note: This bit is effective only if the fieldbus inter-
face is set as the source for this signal by drive
parameters.
Continue normal operation.0
Accelerate to jogging 1 reference.1JOGGING_18
Note:
Bits 4…6 must be 0.
See also section Jogging (page 99).
Jogging 1 disabled.0
Fieldbus control through the embedded fieldbus interface (EFB) 715