STATE/DescriptionValueNameBit
Fault reset if an active fault exists. Proceed to SWITCH-
ON INHIBITED.
0=>1Reset7
Note: This bit is effective only if the fieldbus interface
is set as the source of the reset signal by drive para-
meters.
Continue normal operation.0
Accelerate to inching (jogging) setpoint 1.1Inching 18
Note:
Bits 4...6 must be 0.
See also section Jogging (page 99).
Inching (jogging) 1 disabled.0
Accelerate to inching (jogging) setpoint 2.1Inching 29
See notes at bit 8.
Inching (jogging) 2 disabled.0
Fieldbus control enabled.1Remote cmd10
Control word and reference not getting through to the
drive, except for bits 0...2.
0
Select External Control Location EXT2. Effective if
control location is parameterized to be selected from
fieldbus.
1Ext ctrl loc11
Select External Control Location EXT1. Effective if
control location is parameterized to be selected from
fieldbus.
0
Reserved.12 to 15
736 Fieldbus control through a fieldbus adapter