Not allowed power cable types
Use as motor cablingUse as input power cablingCable type
NoNo
PE
Symmetrical shielded cable with in-
dividual shields for each phase
conductor
Power cable shield
If the cable shield is used as the sole protective earth (PE) conductor, make sure that its
conductivity agrees with the PE conductor requirements.
To effectively suppress radiated and conducted radio-frequency emissions, the cable shield
conductivity must be at least 1/10 of the phase conductor conductivity. The requirements
are easily met with a copper or aluminum shield. The minimum requirement of the motor
cable shield of the drive is shown below. It consists of a concentric layer of copper wires
with an open helix of copper tape or copper wire. The better and tighter the shield, the lower
the emission level and bearing currents.
1 3 4 52
Insulation jacket1
Helix of copper tape or copper wire2
Copper wire shield3
Inner insulation4
Cable core5
Electrical planning guidelines 29