EasyManua.ls Logo

ABB ACS880 - Category C4

ABB ACS880
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Category C4
The drive complies with the C4 category with these provisions:
1. It is ensured that no excessive emission is propagated to neighboring low-voltage
networks. In some cases, the natural suppression in transformers and cables is sufficient.
If in doubt, the supply transformer with static screening between the primary and
secondary windings can be used.
1
2
3
4
5
6
7
8
9
4
6
Equipment6Medium voltage network1
Supply transformer7Neighboring network2
Static screen8Point of measurement3
Drive9Low voltage4
--Equipment (victim)5
2. An EMC plan for preventing disturbances is drawn up for the installation. A template is
available in Technical guide No. 3 EMC compliant installation and configuration for a
power drive system (3AFE61348280 (English)).
3. The motor and control cables are selected, and routed according to the electrical planning
guidelines of the drive. The EMC recommendations are obeyed.
4. The drive is installed according to its installation instructions. The EMC recommendations
are obeyed.
WARNING!
A drive of category C4 is not intended to be used on a low-voltage public network
which supplies domestic premises. Radio frequency interference is expected if
the drive is used on such a network.
Standards and markings 49

Table of Contents

Other manuals for ABB ACS880

Related product manuals