H = Hot swap
Hot swap
System requirements for hot swapping of I/O modules:
Hot-swappable terminal units have the appendix TU5xx-H.
I/O modules as of index F0.
Communication interface modules CI5xx as of index F0.
The index of the module is in the right corner of the label.
NOTICE!
Risk of damage to I/O modules!
Modules with index below F0 can be damaged when inserted or removed from
the terminal unit in a powered system.
NOTICE!
Risk of damage to I/O modules!
Do not perform hot swapping if any I/O module with firmware version lower than
3.0.14 is part of the I/O configuration.
For min. required device index see table below.
Hot swapping is only allowed for I/O modules.
Processor modules and communication interface modules must not be removed
or inserted during operation.
Device Min. required device index for I/O module as of
FW Version 3.0.14
AI523 (-XC) D2
AI531 D4
DX531
2019/11/153ADR024117M02xx, 11, en_US196