14
…4 CONFIGURATION
4.4.2 Regulator Data Page
This page is displayed only when bndLESS is selected at Control Type frame in the Set Up
Control Page
– see Fig. 3.1 and Section 4.10.
Page Header – Regulator Data
Regulator Travel Time
This is the time set for the regulator to travel from the fully
open to the fully closed position or from the fully closed to
the fully open position.
Set the value required in seconds, between 1 and 5000
seconds.
Deadband Setting
The deadband is set as a percentage of the engineering
range span to produce a deadband around the control set
point value. This reduces ‘hunting’ of the regulator.
Set the required value, between 0.0 and 10.0%.
Position Feedback Indication Enable
Select INdCtN to enable the Valve Position frame in the
Operating Page – see
Section 5.2 of the Operating Guide
.
Select NONE to disable the Valve Position frame.
Note. A value is only displayed in the Valve Position
frame if the frame is enabled and the regulator has a
feedback signal.
Return to top of Regulator Data Page,
or
Advance to Set-up Process Variable Input Page.
dAtA
600
dEAdb
1.0
rGL–t
rEGLtr
SEtUP
PrCESS
INdCtN
PSN–Fb