16
…4 CONFIGURATION
4.5.1 Set Up Process Variable Input Page (COMMANDER 300)
If the custom linearizer is to be used (available on COMMANDER 301 only), refer to Section
4.16.
LNtYPI
NONE
tC-K
tC-r
tC-S
tC-J
tC-L
tC-E
rtd
SQrt
tC-t
3 2
5 2
SQrt
NONE
L–UNtI
dEG C
5 2
3 2
tC-b
tC-N
SEtUP
PrCESS
IntYPI
U.Lt
MAMP
VOLt
ohM
tCPL
rtd
(a)
(b)
Page Header – Set Up Process Variable Input.
Process Variable Input Type
Select the input type required:
MU.Lt – Millivolt (≤2000 mV)
MAMP – Current
V.OLt – Voltage
ohM – Resistance
tCPL – Thermocouple *
rtd – Resistance thermometer
*For thermocouple applications using an external fixed
cold junction, select millivolt input type.
Linearizer Type
Select the linearizer type required:
NONE – No linearizer
tC-K – Type K thermocouple
tC-r – Type R thermocouple
tC-S – Type S thermocouple
tC-t – Type T thermocouple
tC-J – Type J thermocouple
tC-L – Type L thermocouple
tC-E – Type E thermocouple
tC-b – Type B thermocouple
tC-N – Type N thermocouple
rtd – Resistance thermometer
SQrt – Square root
3 2 –x
3/2
5 2 –x
5/2
Linearizer Units
Select the temperature units required, °C or °F.
Continued on next page.
Continued on page 18.