28
4.10 Set Up Control Page
Information.
• Control types – Current Proportioning, Time Proportioning (and On/Off), Position-
proportioning (motorized valve control with feedback) and Boundless.
• Heat/cool function can be selected.
• Programmable power-up control modes and outputs.
• Reverse and direct control actions.
• High and low output limits.
…4 CONFIGURATION
Page Header – Set Up Control.
Control Type
Select the control type required:
C–PrOP – current proportioning – see Fig. 4.4.
t–PrOP – time proportioning – see Fig. 4.4.
P–PrOP – position proportioning – motorized valve
with position feedback – see Fig. 4.6.
bNdLSS – boundless – motorized valve without
position feedback. If bNdLSS selected the
self-tune facility is not available and the
Self-tune Page cannot be accessed – see
Fig. 4.7.
Control Mode
Select the control mode required:
SINGLE – normal control mode, used for all
applications except Heat/Cool.
HtCOOL – Heat/Cool control mode – see Fig. 4.5.
Continued on page 30.
SEtUP
CONtrL
C–MOdE
HtCOOL
C–tYPE
C–PrOP
t–PrOP
P–PrOP
P–PrOP
HtCOOL
bNdLSS
SINGLE
SINGLE
bNdLSS
Fig. 4.4 Standard Control Schematic Diagram
P.I.D.
Control
Terms
On/Off
Control
Process
Variable
Set Point
Time Proportioning
Analog Output
Relay or
Digital Output
4 to 20mA
Relay or
Digital Output
COMMANDER 300
Feedback
Process