ETL600 System Test Report
_ EN B1/B11
HE
Test
No.
Test procedure
Test point
Permissible
value
Units
Test
result
B.1 General
B.1.1 Visual checks
Correct wiring of protective earth P7LA, P7LC PE wired [ ]
Correct wiring of power supply P7LA, P7LC polarity ok [ ]
Equipment connected to adequate
voltage source
[ ]
B.2 Check power supply B5LA/B5LC
Upper
Lower
B.2.1
Battery supply 48V DC B5LA (BAT-0V) -46 to –56 V DC [ ] [ ] D
B.2.2
Mains supply 230V AC B5LC (UR-0V) -46 to –52 V DC [ ] [ ] D
B.2.3
Mains supply 115V AC B5LC (UR-0V) -46 to –52 V DC [ ] [ ] D
B.2.4
Ripple on 48V DC B5LA (BAT-0V) < 1 V rms [ ] [ ] D
B.2.5
Ripple on UR (Mains) B5LC (UR-0V) < 1 V rms [ ] [ ] D
B.3 Connect to the equipment,
download configuration and
prepare for tuning & testing
Connect to the equipment
Check communication
between PC and P4LT
[ ]
Download configuration Download successful [ ]
Activate the Tuning & testing dialog
box
Prepare Tuning & testing [ ]
B.4 Change configuration, if necessary
B.5 Transmitter
B.5.1 Programming of the Tx RF filter
Refer to Tx filter tuning instruction
1KHW001492-EN
Upper* Lower
Bandwidth = 8 kHz E5TX Refer to [ ] [ ] D
Bandwidth = 16 kHz E5TX document [ ] [ ] D
Bandwidth = 32 kHz E5TX 1KHW001492 [ ] [ ] D
Center frequency E5TX f
Tx
=________ kHz
B.5.2 Tune Tx RF filter
Upper* Lower
Dialog box 'Tune Tx RF filter' E5TX
Refer to doc.
1KHW001492
[ ] [ ] D
B.5.3 Adjust Tx RF level
Dialog box: Adjust Tx RF level
Click Start/Set
RF hybrid (X200) or RF
line (X175)
value indicated
in dialog box
[ ]
‘Upper’ und ‘Lower’ stands for upper rack / lower rack and applies to 80 W equipment ETL680 only.