5 - Installation
Independent channel configuration (default configuration)
This conguration involves the use of the two input channels (MPPT)
in independent mode. This means that the jumpers between the two
channels (positive and negative) of the DC input terminal block
14
must
not be installed and the switch
17
located on the main board must be
set to “IND”.
Parallel channel configuration
This conguration uses the two input channels (MPPT) connected in
parallel. This means that the jumpers between the two channels (posi-
tive and negative) of the DC input terminal block
14
must be installed
and the switch
17
located on the main board must be set to “PAR”.
14
PAR
4W
3W
IND
MEMORY
CARD
IN MODE
3PH MODE
17
PAR
4W
3W
IND
MEMORY
CARD
IN MODE
3PH MODE
17