2PAA118721 | Quick Installation Guide LD 810HSE Ex 11
Explosion hazard - Do not disconnect equipment unless the power
has been removed or the area is known to be non-hazardous.
Observe relevant national regulations, standards and directives.
This manual does not supersede the relevant national regulations,
standards and directives. These must be observed and have to be
applied according to the national conditions.
Hazardous Location - North American Approval (cULus)
If indicated on the device label, the LD 810HSE Ex Linking Device is suitable for
use in hazardous locations classied as Class 1, Division 2, Groups A, B, C, and
D as well as non-hazardous locations.
The device must be installed in a protective enclosure that meets the require-
ments for resistance to impact and IP54 according to IEC 60529.
Marking for explosion protection: Class I, Div. 2, Groups A, B, C, D.
Explosion hazard - Do not disconnect equipment unless the power
has been removed or the area is known to be non-hazardous.
Explosion hazard - Substitution of any components may impair
suitability for Class I, Division 2.