12 Quick Installation Guide LD 810HSE Ex | 2PAA118721
Hazardous Location - European and International Approval
(ATEX, IECEx)
The equipment was assessed as based on the following standards and editions:
1. IEC 60079-0:2011 Ed. 6, modified Cor. 2012 + Cor. 2013 / EN 60079-0:
2012 + A11:2013
2. IEC 60079-11:2011 Ed. 6 + Corr. 2012 / EN 60079-11:2012
3. IEC 60079-15:2010 Ed. 4 / EN 60079-15:2010
If indicated on the device label or by technical documentation, the
LD 810HSE Ex is suitable for use in gas-Ex atmospheres of Zone 2 in the explo-
sion groups IIA, IIB and IIC in temperature class T4, if accommodated in a tested
enclosure.
– IECEx marking for explosion protection: Ex nA [ic] IIC T4 Gc
– ATEX marking for explosion protection:
II 3G nA [ic] IIC T4 Gc
The Ex protection method [ic] corresponds only to the FF-H1 eldbus interfaces.
The LD 810HSE Ex complies with the applicable standards and regulations and
meets the requirements of Directive 2014/34/EU. The requirements for mounting
the device as part of the system in potentially explosive atmospheres (e. g. IEC/
EN 60079-14) must be strictly adhered to.
For general requirements, rules for installing, commissioning,
maintaining, and the appropriate use of the LD 810HSE Ex in
hazardous atmospheres, refer to Appendix C od the User Manual.