Parameterization
D184B140U02 FSM4000 83
Submenu/parameter Value range Comment
Submenu Set the time-out limits and alarm behavior for values over
or under the DAC value. The DAC value is a criterion for
the amount of coil current.
Alarm DAC Value
Min. value 0 ... 1024 Lower range limit for alarm.
16
Max. value 0 ... 1024 Upper range limit for alarm.
700
Message Off, warning, error Defines the alarm behavior.
Off
Submenu Sets the status of all alarms to "Off" and the max./min.
alarms to the default values.
Alarm Factory Set
Accept Yes, exit via C/CE
Yes → Enter
Submenu
Wiring Error
Submenu Defines alarm behavior in case of an accidental coil
ground.
CoilShtCircGnd
Note: If the coil circuit is being checked (at least every 10
minutes) for an accidental ground, the most recently
acquired flowrate is maintained (approx. 2 s).
Message Off, warning, error
Off
Submenu
Defines alarm behavior in case of a short circuit or a wire
break in the electrode circuit.
Note: This function can only be used after the electrode
zero has been adjusted. For additional information, see
"Submenu Adjustment" on page 85.
Electrode State
Message Off, warning, error
Off