Parameterization
84 FSM4000 D184B140U02
Submenu/parameter Value range Comment
Submenu Preselect the diagnostic measurement values that you
want to display and manage in the Fingerprint data.
Fingerprint
Submenu Assign the rate for Fprt1. The display line for the process
indicator is assigned in the submenu.
Fprt1
Diagnostic
Value
AC volt. coil;
AC curr. coil;
Ohm. coil res.;
Temp. coil;
Insul. coil res.;
Volt. E1; Volt. E2;
Electr. balan.;
Magn. linear;
SNR;
Max. DAC value;
Oprtg. hrs trn;
Oprtg. hrs sens
Select the value:
AC volt. Coil: Coil voltage AC
AC curr. Coil: Coil current AC
Ohm. coil res.: Ohmic resistance of coil
Temp. coil: Coil temperature
Insul. coil res.: Insulation resistance of coil
Volt. E1: AC voltage at electrode 1
Volt. E2: AC voltage at electrode 2
Electr. balan.: Electrode balance
Magn. Linear: Magnetic linearity
SNR: Signal-to-noise ratio
Max. DAC value: Max. DAC value
Oprtg. hrs trn: Operating hours for transmitter
Oprtg. hrs trn: Operating hours for flowmeter sensor
These values are updated only if the status was set to
Warning or Error in the "Alarm Settings" submenu.
AC volt. coil
Data record Current; Prod1;
Prod2; Startup;
Factory;
Hist1; Hist2; Hist3;
Hist4; Hist5; Hist6;
Hist7; Hist8; Hist9
Current: Data record for current value
Prod1: Product1-Fingerprint
Prod2: Product2-Fingerprint
Start: Startup for Fingerprint
Factory: Factory for Fingerprint
Hist1-9: Data record 1 ... 9 for the preceding
measurements
Current
Submenu As for Fprt1 Assign the rate for Fprt1. The display line for the process
indicator is assigned in the submenu.
Fprt4
Submenu Import the current data record in a Fingerprint.
Transfer
As Product1 Copies the current data record in the Fingerprint "as
Product1".
Accept Yes, exit via C/CE
Yes Enter
As Product2 Copies the current data record in the Fingerprint "as
Product2".
Accept Yes, exit via C/CE
Yes Enter

Table of Contents