EasyManua.ls Logo

ABB FSM4000-SE41F - Page 96

ABB FSM4000-SE41F
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameterization
96 FSM4000 D184B140U02
The error registers for diagnostic values are structured as follows:
ID code
_______________________________
Set Off Description
S Signal quality
L Magnetic linearity
B Electrode balance
e Electrode voltage E1
E Electrode voltage E2
D DAC value
I Insulation resistance
T Coil temperature
L Coil resistance
R Coil voltage
C Coil current
ID
code
Register name Content of register
HMx Hist Max Errors Error / Warning: (Max.) values overshot while transmitter is in
operation.
HMi Hist Min Errors Error / Warning: (Min.) values undershot while transmitter is in
operation.
EMx Curr Max Errors Error: (Max.) present available current overshoots.
EMi Curr Min Errors Error: (Min.) present available current undershoots.
WMx Curr Max Warn Warning: (Max.) present available current overshoots.
WMi Curr Min Warn Warning: (Min.) present available current undershoots.
The information EMx _R______B__ indicates Max. Alarm in the current values for the coil
voltage and electrode balance.
The error registers for wiring errors are structured as follows:
ID code
_______________________________
Set Off Description
M Coil short-circuit to
ground
E
Wiring error for
electrodes
ID code Register name Content of register
ConWarn Wiring warning Current warnings for wiring
ConErr Wiring Error Current errors for wiring